Specification: Part Number LFP3000-E4CMB EMC: EN 61326-1:2006, 2004/108/EG Housing material: Plastic PBT Hysteresis: Min. 2 mm, free adjustable Signal voltage HIGH: Vs - 2 V Upper signal level: 20 mA ... 20.5 mA Maximum level change: 500 mm/s Supply voltage: 12 V DC ... 30 V DC Ambient temperature operation: -20 °C ... +60 °C Connection type: Round connector M12 x 1, 5-pin CULus certificate: + Output signal: 1 PNP transistor output (Q1) and 1 PNP / NPN transistor output (Q2) switchable, 4 mA ... 20 mA, 0 V ... 10 V automatic switching depending on the load. Lower signal level: 3.8 mA ... 4 mA Process pressure: -1 bar ... 10 bar Process connection: G ¾ A Probe type: Rope probe Probe length: 3,000 mm Protection class: III Output load: 0 V ... 10 V > 750 Ohm at Uv >= 14 V, 4 mA ... 20 mA < 350 Ohm at Uv > 12 V, 4 mA ... 20 mA < 500 Ohm at Uv > 15 V Conductivity: No limitation Wetted parts: 1.4404, PTFE Accuracy of sensor element: ± 5 mm Medium: Fluids Measurement: Switch, Continuous MTTF: 194.3 a (EN ISO 13849-1) Capacitive load: 100 nF Initialization time: ≤ 5 s Dielectricity constant: ≥ 1.8 with coaxial tube, ≥ 5 for mono rod probe / rope probe IO-Link: + Response time: < 400 ms Inactive area at probe end: 10 mm Max.probe load: 6 Nm Process temperature: -20 °C ... +100 °C Output current: < 100 mA Inactive area at process connector: 25 mm Design: Remote amplifier, cable length 2 m Temperature drift: < 0.1 mm/K Signal voltage LOW: ≤ 2 V Repeatability: ≤ 2 mm Length coaxial cable: 2 m, PVC Resolution: < 2 mm Ambient storage temperature: -40 °C ... +80 °C Inductive load: < 1 H Enclosure rating: IP 67: EN 60529 GOST approval: + Ambient temperature coaxial cable: -20 °C ... +60 °C RoHS certificate: + Power consumption: ≤ 100 mA at 24 V DC without output load