Specification: Part Number 1065363 Housing design: With PMMA viewing window Wetted parts: 316L (Ra ≤ 0,8 µm), PEEK Max.probe load: 6 Nm Hysteresis: Min. 2 mm, free adjustable Output current: < 100 mA RoHS certificate: + Signal voltage HIGH: Vs - 2 V Dielectricity constant: ≥ 1.8 with coaxial tube, ≥ 5 for mono probe Signal voltage LOW: ≤ 2 V Inactive area at process connector: 25 mm Medium: Fluids Supply voltage: 12 V DC ... 30 V DC Output load: 0 V ... 10 V > 750 Ohm at Uv >= 14 V, 4 mA ... 20 mA < 400 Ohm at Uv > 12 V, 4 mA ... 20 mA < 500 Ohm at Uv > 13,5 V Connection type: Round connector M12 x 1, 5-pin Single- and continuous shock: EN 60068-2-27 Measurement: Switch, Continuous Upper signal level: 20 mA ... 20.5 mA UL approval: + Lower signal level: 3.8 mA ... 4 mA Enclosure rating: IP 67: EN 60529, IP 69K: EN 40050 Capacitive load: 100 nF Inactive area at probe end: 10 mm Conductivity: No limitation Process connection: G ¾ A Temperature drift: < 0.1 mm/K Power consumption: ≤ 75 mA at 24 V DC without output load Probe length: 2,700 mm Interference emission: EN 61000-6-4:2007 Initialization time: ≤ 2 s Housing material: 303 Accuracy of sensor element: ± 5 mm EMC: EN 61326-1:2006, 2004/108/EG Ambient storage temperature: -40 °C ... +80 °C MTTF: 194.3 a (EN ISO 13849-1) Inductive load: < 1 H IO-Link: + GOST approval: + Ambient temperature operation: -20 °C ... +60 °C Process temperature: -20 °C ... +150 °C Response time: < 400 ms Process pressure: -1 bar ... 16 bar Resolution: < 2 mm Protection class: III EHEDG approval: + 3-A: - Interference resistance: EN 61000-6-2:2005 Repeatability: ≤ 2 mm