Specification: Part Number 1052082 Accuracy of sensor element: ± 5 mm Signal voltage HIGH: Vs - 2 V Connection type: Round connector M12 x 1, 5-pin Process connection: G ¾ A Upper signal level: 20 mA ... 20.5 mA Lower signal level: 3.8 mA ... 4 mA Initialization time: ≤ 2 s Interference emission: EN 61000-6-4:2007 Inactive area at process connector: 25 mm Housing material: 303 Hysteresis: Min. 2 mm, free adjustable Temperature drift: < 0.1 mm/K Conductivity: No limitation Inductive load: < 1 H Ambient storage temperature: -40 °C ... +80 °C Process pressure: -1 bar ... 16 bar MTTF: 194.3 a (EN ISO 13849-1) Single- and continuous shock: EN 60068-2-27 Process temperature: -20 °C ... +150 °C Power consumption: ≤ 75 mA at 24 V DC without output load RoHS certificate: + GOST approval: + Enclosure rating: IP 67: EN 60529, IP 69K: EN 40050 Capacitive load: 100 nF Medium: Fluids Housing design: With PMMA viewing window Wetted parts: 316L (Ra ≤ 0,8 µm), PEEK EHEDG approval: + Response time: < 400 ms Signal voltage LOW: ≤ 2 V UL approval: + Ambient temperature operation: -20 °C ... +60 °C Probe length: 1,700 mm Max.probe load: 6 Nm Resolution: < 2 mm Output current: < 100 mA 3-A: - IO-Link: + Measurement: Switch, Continuous Supply voltage: 12 V DC ... 30 V DC Protection class: III Output load: 0 V ... 10 V > 750 Ohm at Uv >= 14 V, 4 mA ... 20 mA < 400 Ohm at Uv > 12 V, 4 mA ... 20 mA < 500 Ohm at Uv > 13,5 V Inactive area at probe end: 10 mm Dielectricity constant: ≥ 1.8 with coaxial tube, ≥ 5 for mono probe Repeatability: ≤ 2 mm Interference resistance: EN 61000-6-2:2005 EMC: EN 61326-1:2006, 2004/108/EG