Specification: Part Number 1062273 Temperature drift: < 0.1 mm/K Enclosure rating: IP 67: EN 60529 Lower signal level: 3.8 mA ... 4 mA EMC: EN 61326-1:2006, 2004/108/EG CULus certificate: + Signal voltage LOW: ≤ 2 V Capacitive load: 100 nF Process connection: ¾" NPT Initialization time: ≤ 5 s Housing material: Plastic PBT Inactive area at probe end: 10 mm Probe type: Mono rod probe Response time: < 400 ms Probe length: 1,100 mm Wetted parts: 1.4404, PTFE Signal voltage HIGH: Vs - 2 V IO-Link: + Inactive area at process connector: 25 mm Process temperature: -20 °C ... +100 °C Output current: < 100 mA Maximum level change: 500 mm/s Conductivity: No limitation Ambient temperature operation: -20 °C ... +60 °C Repeatability: ≤ 2 mm Output signal: 1 PNP transistor output (Q1) und 3 PNP / NPN transistor output (Q2...Q4) switchable, 4 mA ... 20 mA, 0 V ... 10 V automatic switching depending on the load. Connection type: Round connector M12 x 1, 8-pin RoHS certificate: + Process pressure: -1 bar ... 10 bar Accuracy of sensor element: ± 5 mm GOST approval: + Power consumption: ≤ 100 mA at 24 V DC without output load Supply voltage: 12 V DC ... 30 V DC Measurement: Switch, Continuous Resolution: < 2 mm Dielectricity constant: ≥ 1.8 with coaxial tube, ≥ 5 for mono rod probe / rope probe Inductive load: < 1 H Max.probe load: 6 Nm Upper signal level: 20 mA ... 20.5 mA Protection class: III Hysteresis: Min. 2 mm, free adjustable MTTF: 194.3 a (EN ISO 13849-1) Design: Standard Output load: 0 V ... 10 V > 750 Ohm at Uv >= 14 V, 4 mA ... 20 mA < 350 Ohm at Uv > 12 V, 4 mA ... 20 mA < 500 Ohm at Uv > 15 V Ambient storage temperature: -40 °C ... +80 °C Medium: Fluids