UE43-4AR3D2

Specification: Part Number 6034775 Input circuit: Single- or dual-channel Operating voltage DC: 24 V DC Opto-electronic protective devices: - Performance level: PL e (EN ISO 13849) Rated operating current (voltage): 5 A (230 V AC) 360 switching cycles/h 5 A (24 V DC) 3600 switching cycles/h Number of enable current contacts: 4 B10d parameter: 31E 05 switching cycles (AC-15, 230 V, I = 5 A) 2 1E 06 switching cycles (DC-15, 230 V, I = 2 A) 71E 06 switching cycles (DC-13, 24 V, I = 1 A) Mechanical life (relay contacts): 11E 07 switching cycles PFHd: 1.30 1E-08 Width: 22.5 mm Maximum power consumption AC: 3.6 VA Number of signalling current contacts: 0 Type of switching amplifier: Main unit Electrical life (relay contacts): 1 1E 06 switching cycles, dependent upon loading, details see operating instructions Safety switches: + Ambient operating temperature from ... to: -25 °C ... 55 °C Emergency stop pushbuttons: + Contact type: Positively driven Type of output: Relay contacts System part: Safety relays External device monitoring: + Reset/restart: Automatic Stop category: 0, EN 60204 Enclosure rating: IP 20 TM (mission time): 20 a Connection type: Plug-in terminals Maximum switching current: 8 A Category: Category 4 (EN ISO 13849) Maximum power consumption DC: 2.1 W Safety integrity level: SIL3 (IEC 61508), SILCL3 (IEC 62061) Cross-circuit detection: +