Specification: Part Number 6024893 Pressure sensitive mats: - Maximum power consumption AC: 4.6 VA Cross-circuit detection: + Synchronous time monitoring: - Reset/restart: Manual / automatic / configurable Width: 22.5 mm Mechanical life (relay contacts): 11E 07 switching cycles Maximum total current: 12 A Operating voltage DC: 24 V DC Safety Switch with mechanical lock: - Opto-electronic protective devices: - Maximum power consumption DC: 2.1 W Two-hand control systems: - Maximum switching current: 6 A Number of enable current contacts: 2 Safety switches: + Ambient operating temperature from ... to: -25 °C ... 55 °C Rated operating current (voltage): 4 A (230 V AC) 360 switching cycles/h 3 A (230 V AC) 3600 switching cycles/h 4 A (24 V DC) 360 switching cycles/h 2.5 A (24 V DC) 3600 switching cycles/h Safety integrity level: SIL3 (IEC 61508), SILCL3 (IEC 62061) Electrical life (relay contacts): 11E 05 switching cycles, dependent upon loading, details see operating instructions B10d parameter: 1.26 1E 06 switching cycles (AC-15, 230 V, I = 1.5 A) 5.91E 06 switching cycles (AC-15, 230 V, I = 0.75 A) 4.351E 05 switching cycles (DC-13, 24 V, I = 2.5 A) 11E 07 switching cycles (DC-13, 24 V, I = 0.63 A) Type of output: Relay contacts Connection type: Screw-type terminals Performance level: PL e (EN ISO 13849) Emergency stop pushbuttons: + PFHd: 3.0 1E-08 TM (mission time): 20 a Opto-electronic protective devices with RES/EDM: - External device monitoring: + Category: Category 4 (EN ISO 13849) Type of switching amplifier: Main unit Opto-electronic protective devices without RES/EDM: - Operating voltage AC: 24 V AC Enclosure rating: IP 20 Number of signalling current contacts: 1 System part: Safety relays Stop category: 0, EN 60204 Input circuit: Single- or dual-channel Contact type: Positively driven