Specification: Part Number 1062257 Conductivity: No limitation Resolution: < 2 mm Max.probe load: 6 Nm Capacitive load: 100 nF Protection class: III Inductive load: < 1 H Ambient storage temperature: -40 °C ... +80 °C Hysteresis: Min. 2 mm, free adjustable Process pressure: -1 bar ... 10 bar Design: Standard Medium: Fluids Output signal: 1 PNP transistor output (Q1) und 3 PNP / NPN transistor output (Q2...Q4) switchable, 4 mA ... 20 mA, 0 V ... 10 V automatic switching depending on the load. Measurement: Switch, Continuous IO-Link: + Output load: 0 V ... 10 V > 750 Ohm at Uv >= 14 V, 4 mA ... 20 mA < 350 Ohm at Uv > 12 V, 4 mA ... 20 mA < 500 Ohm at Uv > 15 V Wetted parts: 1.4404, PTFE Supply voltage: 12 V DC ... 30 V DC GOST approval: + Upper signal level: 20 mA ... 20.5 mA Initialization time: ≤ 5 s CULus certificate: + Temperature drift: < 0.1 mm/K Inactive area at probe end: 10 mm Inactive area at process connector: 25 mm MTTF: 194.3 a (EN ISO 13849-1) Maximum level change: 500 mm/s Probe length: 1,400 mm Lower signal level: 3.8 mA ... 4 mA Repeatability: ≤ 2 mm Ambient temperature operation: -20 °C ... +60 °C Response time: < 400 ms Process connection: G ¾ A Enclosure rating: IP 67: EN 60529 Accuracy of sensor element: ± 5 mm Output current: < 100 mA Power consumption: ≤ 100 mA at 24 V DC without output load Process temperature: -20 °C ... +100 °C Connection type: Round connector M12 x 1, 8-pin Dielectricity constant: ≥ 1.8 with coaxial tube, ≥ 5 for mono rod probe / rope probe RoHS certificate: + Signal voltage HIGH: Vs - 2 V Probe type: Mono rod probe Housing material: Plastic PBT EMC: EN 61326-1:2006, 2004/108/EG Signal voltage LOW: ≤ 2 V