Specification: Part Number 1071084 Output current: < 100 mA Probe type: Mono rod probe Temperature drift: < 0.1 mm/K Process pressure: -1 bar ... 10 bar CULus certificate: + Signal voltage LOW: ≤ 2 V Measurement: Switch, Continuous Inactive area at probe end: 10 mm Probe length: 300 mm Process temperature: -20 °C ... +100 °C Power consumption: ≤ 100 mA at 24 V DC without output load Protection class: III Wetted parts: 1.4404, PTFE Inductive load: < 1 H Length coaxial cable: 3.3 m, PVC Medium: Fluids Signal voltage HIGH: Vs - 2 V Enclosure rating: IP 67: EN 60529 Supply voltage: 12 V DC ... 30 V DC Upper signal level: 20 mA ... 20.5 mA Accuracy of sensor element: ± 5 mm Initialization time: ≤ 5 s Design: Remote amplifier, cable length 3 m Ambient temperature operation: -20 °C ... +60 °C Lower signal level: 3.8 mA ... 4 mA Dielectricity constant: ≥ 1.8 with coaxial tube, ≥ 5 for mono rod probe / rope probe IO-Link: + Hysteresis: Min. 2 mm, free adjustable Process connection: G ¾ A Response time: < 400 ms MTTF: 194.3 a (EN ISO 13849-1) Ambient temperature coaxial cable: -20 °C ... +60 °C Ambient storage temperature: -40 °C ... +80 °C EMC: EN 61326-1:2006, 2004/108/EG Output signal: 1 PNP transistor output (Q1) and 1 PNP / NPN transistor output (Q2) switchable, 4 mA ... 20 mA, 0 V ... 10 V automatic switching depending on the load. Connection type: Round connector M12 x 1, 5-pin Resolution: < 2 mm Capacitive load: 100 nF RoHS certificate: + GOST approval: + Housing material: Plastic PBT Inactive area at process connector: 25 mm Conductivity: No limitation Max.probe load: 6 Nm Maximum level change: 500 mm/s Output load: 0 V ... 10 V > 750 Ohm at Uv >= 14 V, 4 mA ... 20 mA < 350 Ohm at Uv > 12 V, 4 mA ... 20 mA < 500 Ohm at Uv > 15 V Repeatability: ≤ 2 mm