Specification: Part Number 6049101 Impuls/frequency output: 0 kHz ... 10 kHz Repeatability: &le; 0.5 % Weight: 340 g Inductive load: 1 H Lower signal level: 3.8 mA ... 4 mA Output current: < 100 mA Signal voltage LOW: &le; 2 V Upper signal level: 20 mA ... 20.5 mA Supply voltage: 18 V DC ... 30 V DC Medium: Fluids Output load: < 500 Ohm Maximum flow: 21 l/min Wetted parts: PSU Process connection: Clamp (DIN 11864-3) Nominal width measuring tube: NW 10 Inlet zone: 20 cm Enclosure rating: IP 67 Accuracy of sensor element: 2 % (of final value) Ambient temperature operation: 0 °C ... +60 °C Connection type: Round connector M12 x 1, 5-pin Capacitive load: 100 nF Outlet zone: 0 cm Resolution: 0.003 l/min Process pressure: Max. 16 bar Process temperature: 0 °C ... +80 °C Initialization time: &le; 5 s Output signal: Analog output: 4 mA ... 20 mA, 0 mA ... 20 mA current flow and temperature 1 pulse/status output: transistor output for flow rate meter, empty pipe detection, flow monitoring, dosing output, flow direction (depending on type) Housing material: PSU Response time: Filter off 100 ms, filter low 300 ms, filter medium 1 s, filter strong 4.2 s Conductivity: No limitation Ambient storage temperature: -20 °C ... +70 °C Puls width: &le; 1 s Protection class: III Power consumption: &le; 180 mA Signal voltage HIGH: Vs - 2 V Minimim flow: 0.3 l/min Ripple: &le; 5 Vpp