MAIN CHARACTERISTICS range of product MODICON TM3 SAFETY product or component type SAFETY MODULE device short name TM3SAK safety module application MRG SPSWTMAT EGS CRTN MTRG function of module emergency stop monitoring 1-channel wiring safety level CAN REACH PL ECATEGORY 4 ENISO 13849-12008 COMPLEMETARY CHARACTERISTICS safety reliability data DC = 95 ENISO 13849-1 synchronisation time between inputs unlimited connections - terminals CAPTIVE SCREW CLAMP TERMINALS REMOVABLE TERMINAL BLOCK 1 X 0.2...1 X 2.5 MM FLEXIBLE WITHOUT CABLE END 13-14 23-24 33-34 number of safety circuits 3 NO (relay instantaneous opening) maximum switching voltage 230 V utilisation category AC-15 at 50 Hz (relay instantaneous opening) [Us] rated supply voltage 24 V DC - 15...20 power consumption in W 0.2 W 5 V input protection type INTERNAL ELECTRONIC [Uc] control circuit voltage 24 V DC max cable distance between devices 30 M breaking capacity 360 VA HOLDING AC-15 B300 RELAY OUTPUT breaking capacity 4 A 24 V 50 MS DC-13 RELAY OUTPUT output thermal current 6 A PER RELAY RELAY OUTPUT [Ith] conventional free air thermal current 18 A associated fuse rating 4 A GG OR GL RELAY OUTPUT ENIEC 60947-5-1 minimum output current 10 MA RELAY OUTPUT output voltage 10 V RELAY OUTPUT response time on input open