MAIN CHARACTERISTICS range of product MODICON TM3 SAFETY product or component type SAFETY MODULE device short name TM3SAF safety module application F EMERGENCY STOP+SWITCH MNTRG function of module emergency stop monitoring 1-channel wiring safety level CAN REACH PL ECATEGORY 4 ENISO 13849-12008 COMPLEMETARY CHARACTERISTICS safety reliability data DC = 95 ENISO 13849-1 synchronisation time between inputs unlimited connections - terminals CAPTIVE SCREW CLAMP TERMINALS REMOVABLE TERMINAL BLOCK 1 X 0.2...1 X 2.5 MM FLEXIBLE WITHOUT CABLE END 13-14 23-24 33-34 number of safety circuits 3 NO (relay instantaneous opening) maximum switching voltage 230 V utilisation category AC-15 at 50 Hz (relay instantaneous opening) [Us] rated supply voltage 24 V DC - 15...20 power consumption in W 0.2 W 5 V input protection type INTERNAL ELECTRONIC [Uc] control circuit voltage 24 V DC max cable distance between devices 30 M breaking capacity 360 VA HOLDING AC-15 B300 RELAY OUTPUT breaking capacity 4 A 24 V 50 MS DC-13 RELAY OUTPUT output thermal current 6 A PER RELAY RELAY OUTPUT [Ith] conventional free air thermal current 18 A associated fuse rating 4 A GG OR GL RELAY OUTPUT ENIEC 60947-5-1 minimum output current 10 MA RELAY OUTPUT output voltage 10 V RELAY OUTPUT response time on input open