MAIN CHARACTERISTICS range TESYS product name TESYS T device short name LTMR product or component type MOTOR CONTROLLER device application EQUIPMENT MNTRG AND CONTROL measurement current 0.4...8 A [Us] rated supply voltage 100...240 V AC 5060 HZ current consumption 8...62.8 MA supply voltage limits 93.5...264 V AC communication port protocol MODBUS bus type MODBUS 2-WIRE RS 485 INTERFACE ADDRESSING 1...247 TRANSMISSION RATE 1.2...19.2 KBITS RJ45 WITH 2 SHIELDED TWISTED PAIRS COMPLEMETARY CHARACTERISTICS [Ui] rated insulation voltage 690 V CONFORMING TO ENIEC 60947-1 [Uimp] rated impulse withstand voltage 4 KV FOR SUPPLY INPUTS AND OUTPUTS CONFORMING TO ENIEC 60947-4-1 short-circuit withstand 100 KA CONFORMING TO ENIEC 60947-4-1 associated fuse rating 4 A GG FOR OUTPUT protection type EARTH-LEAKAGE PROTECTION network and machine diagnosis type PH FLT + E FAULT TRIP COUNTERS logic input number 6 input current 3.1 MA AT 100 V input/output type LOGIC INPUT 0...40 V AND 0.1 A overvoltage category III connection pitch 5.08 MM connections - terminals connector, 1 flexible cable with cable end 0.25...2.5 mm² /AWG 24...AWG 14 for control circuit tightening torque 0.5...0.6 N.M 3 MM FLAT SCREWDRIVER FOR CONTROL CIRCUIT pollution degree 3 electromagnetic compatibility ELECTROSTATIC DISCHARGE 3 8 KV AIR 6 KV CONTACT CONFORMING TO ENIEC 61000-4-2 width 91 MM height 61 MM depth 122.5 MM product weight 0.53 KG web services WEB SERVER compatibility code LTMR