MAIN CHARACTERISTICS range TESYS product name TESYS T device short name LTMR product or component type MOTOR CONTROLLER device application EQUIPMENT MNTRG AND CONTROL measurement current 0.4...8 A [Us] rated supply voltage 24 V DC current consumption 56...127 MA supply voltage limits 20.4...26.24 V DC communication port protocol MODBUS TCP ETHERNET IP bus type ETHERNET IEEE 802.3 INTERFACE ADDRESSING 0...159 TRANSMISSION RATE 10...100 MBITS RJ45 WITH 2 SHIELDED TWISTED PAIRS COMPLEMETARY CHARACTERISTICS [Ui] rated insulation voltage 690 V CONFORMING TO ENIEC 60947-1 [Uimp] rated impulse withstand voltage 6 KV FOR CURRENT OR VOLTAGE MEASUREMENT CIRCUIT CONFORMING TO ENIEC 60947-4-1 short-circuit withstand 100 KA CONFORMING TO ENIEC 60947-4-1 associated fuse rating 4 A GG FOR OUTPUT protection type EARTH-LEAKAGE PROTECTION network and machine diagnosis type PH FLT + E FAULT TRIP COUNTERS logic input number 6 input current 7 MA input/output type LOGIC INPUT < 15 V AND 2 A...15 MA FOR 15 MS AT STATE 1 maximum output switching frequency 2 HZ load current 5 A AT 250 V AC FOR LOGIC OUTPUT permissible power 480 VA AC-15 IE = 2 A 500000 CYCLES OUTPUT operating rate 1800 CYCH contacts type and composition 1 NO + 1 NC FAULT SIGNAL metering type EARTH-FAULT CURRENT measurement accuracy 5...15 EARTH FAULT CURRENT INTERNAL MEASUREMENT FOR CURRENT > 0.1 A overvoltage category III connection pitch 5.08 MM connections - terminals connector, 1 flexible cable with cable end 0.25...2.5 mm² /AWG 24...AWG 14 for control circuit tightening torque 0.5...0.6 N.M 3 MM FLAT SCREWDRIVER FOR CONTROL CIRCUIT pollution degree 3 electromagnetic compatibility ELECTROSTATIC DISCHARGE 3 8 KV AIR 6 KV CONTACT CONFORMING TO ENIEC 61000-4-2 width 91 MM height 61 MM depth 122.5 MM product weight 0.53 KG web services WEB SERVER compatibility code LTMR