MAIN CHARACTERISTICS range of product RED range of product ACTI 9 product or component type RESIDUAL CRRT CCT BRKER RCCB device short name REDTEST protection type RECLOSER poles description 2P neutral position RIGHT signal contacts composition 1 NO OR INTERMITTENT 1 HZ [In] rated current 40 A earthing system TN-S network type AC earth-leakage sensitivity 30 MA COMPLEMETARY CHARACTERISTICS device location in system OUTGOER network frequency 50 HZ [Ue] rated operational voltage 230 V AC 50 HZ PHASE TO NEUTRAL reset FAULT RESET EARTH LEAKAGE test function AUTO TEST earth-leakage protection time delay INSTANTANEOUS earth-leakage protection class TYPE A leakage resistance 120 KOHM [Im] rated making and breaking capacity IDM 630 A 230 V rated conditional short-circuit current C120 : Inc 6 kA 40 A [Ui] rated insulation voltage 500 V [Uimp] rated impulse withstand voltage 4 KV control type TOGGLE local signalling 2 LEDS type of setting AUTOTEST signalling circuit voltage AC 12...230 V signalling output current 0.6 MA MIN mounting mode FIXED mounting support 35 MM SYMMETRICAL DIN RAIL 9 mm pitches 10 height 115 MM width 89.2 MM depth 79.5 MM product weight 0.37 KG mechanical durability 1000 CYCLES OPEN-CLOSE connections - terminals GUARD TUNNEL TERMINAL 35 MM RIGID auxiliary connection terminal TUNNEL TYPE TERMINAL FLEXIBLE 2.5 MM wire stripping length 12 MM tightening torque power circuit : 2 N.m market segment SMALL COMMERCIAL compatibility code REDTEST