MAIN CHARACTERISTICS range of product RED range of product ACTI 9 product or component type RESIDUAL CRRT CCT BRKER RCCB device short name REDS protection type RECLOSER poles description 4P neutral position LEFT signal contacts composition 1NO OR 1NC OR INTERMITTENT 1HZ [In] rated current 63 A earthing system TN-S network type AC earth-leakage sensitivity 30 MA COMPLEMETARY CHARACTERISTICS device location in system OUTGOER network frequency 50 HZ [Ue] rated operational voltage 400 V AC 50 HZ PHASE TO NEUTRAL reset FAULT RESET EARTH LEAKAGE test function MANUAL AT 170 V earth-leakage protection time delay INSTANTANEOUS earth-leakage protection class TYPE A [Im] rated making and breaking capacity IDM 630 A 400 V rated conditional short-circuit current gL63 : Inc 6 kA 25 A gL [Ui] rated insulation voltage 500 V [Uimp] rated impulse withstand voltage 4 KV control type TOGGLE local signalling 2 LEDS type of setting INSUL FLT PRESENCE MONITORING signalling circuit voltage AC 5...230 V signalling output current 0.6 MA MIN mounting mode FIXED mounting support 35 MM SYMMETRICAL DIN RAIL 9 mm pitches 14 height 98 MM width 125 MM depth 79.5 MM embedding depth 73.5 MM product weight 0.72 KG mechanical durability 4000 CYCLES OPEN-CLOSE connections - terminals GUARD TUNNEL TERMINAL 35 MM RIGID auxiliary connection terminal TUNNEL TYPE TERMINAL FLEXIBLE 2.5 MM wire stripping length 12 MM tightening torque power circuit : 2 N.m market segment SMALL COMMERCIAL compatibility code REDS