NJ5-30GK-S1N-5M

General specifications Switching element function NAMUR, NO Rated operating distance 5 mm Installation flush in mild steel Output polarity Safety Function Assured operating distance 0 ... 4.05 mm Reduction factor r Al 1 Reduction factor r Cu 1 Reduction factor r 304 0 Safety Integrity Level (SIL) up to SIL3 acc. to IEC 61508 Danger! In safety-related applications the sensor must be operated with a qualified fail safe interface from Pepperl+Fuchs, such as KFD2-SH-EX1. Consider the exida Functional Safety Assessment document which is available on www.PEPPERL+FUCHS.com as an integral part of this product's documentation. Nominal ratings Nominal voltage 8 V Switching frequency 0 ... 150 Hz Suitable for 2:1 technology yes , with reverse polarity protection diode Current consumption Measuring plate not detected max. 1 mA Measuring plate detected greater or equal 3 mA Approvals and certificates UL approval cULus Listed, General Purpose CSA approval cCSAus Listed, General Purpose CCC approval CCC approval / marking not required for products rated less than or equal to 36 V Ambient conditions Ambient temperature -25 ... 100 °C (-13 ... 212 °F) Mechanical specifications Connection type cable silicone , 5 m Core cross-section 0.75 mm 2 Housing material PP Sensing face PP Housing diameter 30 mm Degree of protection IP68 Note only for non-ferrous metal General information Use in the hazardous area see instruction manuals Category 1G- 2G- 1D