Specification: Part Number 1055428 Shock/vibration: 30 g, 11 ms / 10 ... 55 Hz, 1 mm EMC: According to EN 60947-5-2 Output current Ia: ≤ 200 mA Sensing range Sn: 4 mm Cable diameter: Ø 3.7 mm Sensing face material: Plastic, VISTAL Temperature drift (of Sr): ± 10 % Installation type: Flush Note: The values are reference values which may vary Supply voltage: 10 V DC ... 30 V DC D: 12 mm Ambient operating temperature: -25 °C ... +75 °C Aluminum (Al): 0.4 Cable material: PVC Time delay before availability: ≤ 100 ms Power-up pulse protection: + Switching frequency: 2,000 Hz Dimensions (W x H x D): 12 mm x 26 mm x 40 mm Copper (Cu): 0.3 A: 0 mm E: 0 mm Power consumption: ≤ 10 mA Remark: Associated graphic see "Installation" Tightening torque, max.: ≤ 1 Nm Output function: NO Ripple: ≤ 10 % G: 0 mm Reverse polarity protection: + Repeatability: ≤ 2 % Electrical wiring: DC 3-wire Short-circuit protection: + Voltage drop: ≤ 2 V Housing material: Plastic, VISTAL F: 32 mm Hysteresis: 5 % ... 15 % Assured sensing range Sa: 3.24 mm Stainless steel (V2A, 304): 0.7 Design: Rectangular Connection type: Cable, 3-wire, 2 m Conductor cross-section: 0.25 mm² Switching output: PNP B: 12 mm Enclosure rating: IP 67 IP 68 Brass (Br): 0.4 C: 12 mm