Specification: Part Number 1044604 Thread size: M30 x 1.5 C: 30 mm Power consumption: ≤ 10 mA Tightening torque, max.: 100 Nm Housing length: 70 mm Design: Cylindrical Note: The values are reference values which may vary Remark: Associated graphic see "Installation" Connection type: Cable, 3-wire, 6 m Thread length: 54 mm EMC: According to EN 60947-5-2 Housing cap material: Plastic, PA6 Ripple: ≤ 10 % Aluminum (Al): Ca. 0.45 Time delay before availability: ≤ 125 ms Supply voltage: 10 V DC ... 30 V DC Assured sensing range Sa: 8.1 mm Switching output: NPN Enclosure rating: IP 67 Cable material: PVC Temperature drift (of Sr): ± 10 % Electrical wiring: DC 3-wire Switching frequency: 500 Hz Voltage drop: ≤ 2 V Stainless steel (V2A, 304): Ca. 0.8 Housing material: Metal, Nickel-plated brass Installation type: Flush Sensing range Sn: 10 mm Power-up pulse protection: + Ambient operating temperature: -25 °C ... 75 °C Shock/vibration: 30 g, 11 ms/10 Hz ... 55 Hz, 1 mm Output function: NO Repeatability: ≤ 2 % Carbon steel St37 (Fe): 1 D: 30 mm Hysteresis: 5 % ... 15 % Copper (Cu): Ca. 0.4 F: 80 mm Brass (Br): Ca. 0.4 B: 30 mm Output current Ia: ≤ 200 mA Housing: Standard Reverse polarity protection: + Short-circuit protection: +