MAIN CHARACTERISTICS network rated voltage 400 V - AC AT 50 HZ reactive power rating 50 KVAR operating mode FIXED range VARSET range of product VARSET device short name VARSET FIXED product or component type CAPACITOR BANK COMPLEMETARY CHARACTERISTICS network pollution level LOW POLLUTED [Gh/Sn] harmonic pollution rate 15...25 PC [THDU] total harmonic distorsion of voltage > 3...4 power per step 50 KVAR step composition 50 location of connection TOP internal voltage transformer 400230 V - 100 VA capacitor technology VARPLUSCAN poles description 3P capacitance tolerance - 5 PT TO 10 PT [Ui] rated insulation voltage 690 V [Uimp] rated impulse withstand voltage 6 KV maximum permissible voltage 1.1 X UN 8 HOURS OVER 24 HOURS CONFORMING TO IEC 60831 [Imp] maximum permanent current CAPACITOR 1.8 X IN AT 400 V CONFORMING TO IEC 60831 protection type CIRCUIT BREAKER PROTECTION breaking capacity 35 KA ICU accessibility for operation FRONT colour RAL 7035 (grey) maximum weight 64 KG height 700 MM width 600 MM depth 300 MM provided equipment AUXILIARY TRANSFORMER function available GENSET SHEDDING CONTACT