MAIN CHARACTERISTICS network rated voltage 400 V - AC AT 50 HZ reactive power rating 50 KVAR operating mode FIXED range VARSET range of product VARSET device short name VARSET FXD W DETUNED REACTORS product or component type CAPACITOR BANK COMPLEMETARY CHARACTERISTICS network pollution level POLLUTED [Gh/Sn] harmonic pollution rate 25...50 PC [THDU] total harmonic distorsion of voltage > 4...7 tuning factor 4.2 tuning frequency 210 HZ power per step 50 KVAR step composition 50 location of connection BOTTOM internal voltage transformer 400230 V - 400 VA capacitor technology VARPLUSCAN + DETUNED REACTORS poles description 3P capacitance tolerance - 5 PT TO 10 PT [Ui] rated insulation voltage 690 V [Uimp] rated impulse withstand voltage 8 KV maximum permissible voltage 1.1 X UN 8 HOURS OVER 24 HOURS CONFORMING TO IEC 60831 [Imp] maximum permanent current CAPACITOR 1.8 X IN AT 480 V CONFORMING TO IEC 60831 protection type CIRCUIT BREAKER PROTECTION [Icw] rated short-time withstand current 30 KA AT 1 S ICW accessibility for operation FRONT colour RAL 7035 (grey) maximum weight 334 KG height 1300 MM width capacitor : 800 mm depth 300 MM provided equipment AUXILIARY TRANSFORMER function available GENSET SHEDDING CONTACT