MAIN CHARACTERISTICS network rated voltage 400 V - AC AT 50 HZ reactive power rating 90 KVAR operating mode AUT range VARSET range of product VARSET device short name VARSET AUTOMATIC product or component type CAPACITOR BANK COMPLEMETARY CHARACTERISTICS network pollution level NO POLLUTED [Gh/Sn] harmonic pollution rate 0...15 PC [THDU] total harmonic distorsion of voltage 0...3 PC step sequences 1.1.2 power per step 15 KVAR step composition 2X15 + 2X30 location of connection TOP internal voltage transformer 400230 V - 160 VA controller type VARPLUS LOGIC VPL6 MODBUS capacitor technology EASYCAN poles description 3P capacitance tolerance - 5 PT TO 10 PT [Ui] rated insulation voltage 690 V [Uimp] rated impulse withstand voltage 6 KV maximum permissible voltage 1.1 X UN 8 HOURS OVER 24 HOURS CONFORMING TO IEC 60831 [Imp] maximum permanent current CAPACITOR 1.5 X IN AT 400 V CONFORMING TO IEC 60831 protection type CIRCUIT BREAKER PROTECTION breaking capacity 35 KA ICU accessibility for operation FRONT colour RAL 7035 (grey) maximum weight 73 KG height 800 MM width 600 MM depth 250 MM provided equipment AUXILIARY TRANSFORMER function available GENSET SHEDDING CONTACT