MAIN CHARACTERISTICS network rated voltage 400 V - AC AT 50 HZ reactive power rating 20 KVAR operating mode AUT range VARSET range of product VARSET device short name VARSET AUTOMATIC product or component type CAPACITOR BANK COMPLEMETARY CHARACTERISTICS network pollution level NO POLLUTED [Gh/Sn] harmonic pollution rate 0...15 PC [THDU] total harmonic distorsion of voltage 0...3 PC step sequences 1.1.2 power per step 5 KVAR step composition 2X5 + 10 location of connection TOP controller type VARPLUS LOGIC VPL6 MODBUS capacitor technology EASYCAN poles description 3P capacitance tolerance - 5 PT TO 10 PT [Ui] rated insulation voltage 500 V [Uimp] rated impulse withstand voltage 6 KV maximum permissible voltage 1.1 X UN 8 HOURS OVER 24 HOURS CONFORMING TO IEC 60831 [Imp] maximum permanent current CAPACITOR 1.5 X IN AT 400 V CONFORMING TO IEC 60831 protection type CIRCUIT BREAKER PROTECTION breaking capacity 15 KA ICU accessibility for operation FRONT colour RAL 7035 (grey) maximum weight 57 KG height 650 MM width 500 MM depth 250 MM provided equipment AUXILIARY TRANSFORMER function available GENSET SHEDDING CONTACT