MAIN CHARACTERISTICS range of product TESYS U range TESYS product name TESYS U device short name LUCB product or component type ADVANCED CONTROL UNIT product specific application BASIC PROT AND ADV FCT COM product compatibility LUFC00 utilisation category AC-41 motor power kW 9 KW AT 690 V AC 5060 HZ thermal protection adjustment range 3...12 A [Uc] control circuit voltage 110..220 V DC thermal overload class CLASS 10 - FREQUENCY LIMIT 40...60 HZ - TEMPERATURE COMPENSATION -25...70 C - CONFORMING TO IEC 60947-6-2 COMPLEMETARY CHARACTERISTICS main function available EARTH FAULT PROTECTION mounting mode PLUG IN mounting location FRONT SIDE control circuit voltage limits 88...242 V FOR DC CIRCUIT 110...220 V IN OPERATION typical current consumption 25 MA AT 110...240 V AC I RMS SEALED WITH LUB12 operating time 35 MS OPENING WITH LUB12 FOR CONTROL CIRCUIT load type 3-PHASE MOTOR - COOLING SELF-COOLED tripping threshold 14.2 X IR +- 20 [Ui] rated insulation voltage 600 V CONFORMING TO UL 508 [Uimp] rated impulse withstand voltage 6 KV CONFORMING TO IEC 60947-6-2 safe separation of circuit 400 V SELV BETWEEN THE CONTROL AND AUXILIARY CIRCUITS CONFORMING TO IEC 60947-1 compatibility code LUCB