MAIN CHARACTERISTICS range of product TESYS U range TESYS product name TESYS U device short name LUB product or component type NON REVERSING POWER BASE device application MOTOR poles description 3P suitability for isolation YES [Ith] conventional free air thermal current 32 A utilisation category AC-41 [Uc] control circuit voltage 24 V AC 5060 HZ COMPLEMETARY CHARACTERISTICS auxiliary contact composition 1 NO + 1 NC auxiliary contacts type TYPE LINKED CONTACTS 1 NO + 1 NC CONFORMING TO IEC 60947-4-1 [Ue] rated operational voltage 230 V network frequency 40..60 HZ [Ie] rated operational current 21 A AT 690 V [Ics] rated service breaking capacity 10 KA 500 V typical current consumption 200 MA AT 24 V DC I MAXIMUM WHILE CLOSING WITH LUCM safety reliability level B10d 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 operating time 35 MS OPENING WITH LUCA LUCB LUCC LUCD LUCM FOR CONTROL CIRCUIT mechanical durability 15000000 CYCLES operating rate 60 CYCMN [Ui] rated insulation voltage 600 V CONFORMING TO UL 508 [Uimp] rated impulse withstand voltage 6 KV CONFORMING TO IEC 60947-6-2 safe separation of circuit 400 V SELV BETWEEN THE CONTROL AND AUXILIARY CIRCUITS CONFORMING TO IEC 60947-1 APPENDIX N connections - terminals power circuit : screw clamp terminals 1 cable 1...10 mm² - cable stiffness: rigid - without cable end tightening torque control circuit : 0.8...1.2 N.m - with screwdriver 5 mm flat width 45 MM height 145 MM depth 126 MM product weight 0.865 KG compatibility code LUB