MAIN CHARACTERISTICS range of product CANALIS range CANALIS product name KT product or component type BUSBAR TRUNKING busbar description DISTRIBUTION LENGTH device short name KTC tap-off unit compatibility bolt-on tap-off unit from Canalis - KT device application HIGH POWER DISTRIBUTION material COPPER [Ie] rated operational current 4000 A at 35 °C polarity 3L+N+PE number of tap-off outlets 1 nominal output current 400...1250 A earth conductor STANDARD EARTH short-circuit level STANDARD VERSION length 2000 MM provided equipment TRUNKING UNIT COMPLEMETARY CHARACTERISTICS housing material POLYESTER FILM contacts material COPPER [Ue] rated operational voltage 1000 V network frequency 50 60 HZ [Ui] rated insulation voltage 1000 V [Icw] rated short-time withstand current 90 KA [Ipk] rated peak withstand current 198 KA electrical connection BOLTED CONNECTION radiated magnetic field 2.1 T thermal stress limit 8100 A.S THDI 33...100 %, maximum load current: 2500 A voltage drop with cos Æ=1, 0.001 V at 50 Hz with 1A for 100 m long linear resistance L - PE : Rb0 20 °C= 0.135 mΩ/m impedance method mounting mode BY HOOK mounting support PENDANT installation direction HORIZONTAL neutral position RIGHT standards IEC 61439-1 dimension type FIX width 140 MM height 324 MM colour RAL 9001 : white product weight 184 KG linear load 92 KGM