MAIN CHARACTERISTICS range of product TESYS GV7 range TESYS product name TESYS GV7 device short name GV7R product or component type CIRCUIT BREAKER device application MOTOR poles description 3P network type AC utilisation category AC-3 CONFORMING TO IEC 60947-4-1 network frequency 5060 HZ CONFORMING TO IEC 60947-4-1 breaking capacity 10 KA ICU AT 690 V AC 5060 HZ CONFORMING TO IEC 60947-2 [Ics] rated service short-circuit breaking capacity 100 AT 230...240 V AC 5060 HZ CONFORMING TO IEC 60947-2 thermal protection adjustment range 132...220 A trip unit technology THERMAL-MAGNETIC COMPLEMETARY CHARACTERISTICS mounting mode BY CLIPS mounting support FLUSH mounting position VERTICAL motor power kW 110 KW AT 400...415 V AC 5060 HZ control type ROCKER LEVER [In] rated current 220 A [Ue] rated operational voltage 690 V AC 5060 HZ CONFORMING TO IEC 60947-2 [Ui] rated insulation voltage 750 V AC 5060 HZ CONFORMING TO IEC 60947-2 [Ith] conventional free air thermal current 220 A CONFORMING TO IEC 60947-4-1 [Uimp] rated impulse withstand voltage 8 KV CONFORMING TO IEC 60947-2 power dissipation per pole 14.5 W power dissipation per pole 14.5 W mechanical durability 20000 CYCLES electrical durability 10000 CYCLES FOR AC-3 AT 440 V IN operating rate 25 CYCH rated duty CONTINUOUS CONFORMING TO IEC 60947-4-1 connection pitch 35 MM WITHOUT SPREADERS connections - terminals bars tightening torque 10 N.M - ON SCREW - SCREW M6 mechanical robustness SHOCKS 15 GN FOR 11 MS CONFORMING TO IEC 60068-2-27 suitability for isolation YES CONFORMING TO IEC 60947-1 phase failure sensitivity YES CONFORMING TO IEC 60947-4-1 7-2-1-5-2 height 125 MM width 105 MM depth 111 MM product weight 2.35 KG compatibility code GV7RS