MAIN CHARACTERISTICS range of product TESYS GV2 range TESYS product name TESYS GV2 device short name GV2ME product or component type CIRCUIT BREAKER device application MOTOR trip unit technology THERMAL-MAGNETIC COMPLEMETARY CHARACTERISTICS poles description 3P network type AC utilisation category AC-3 CONFORMING TO IEC 60947-4-1 network frequency 5060 HZ CONFORMING TO IEC 60947-4-1 mounting mode BY CLIPS mounting support RAIL mounting position HORIZONTAL motor power kW 0.25 KW AT 400415 V AC 5060 HZ breaking capacity 100 KA ICU AT 230240 V AC 5060 HZ CONFORMING TO IEC 60947-2 [Ics] rated service short-circuit breaking capacity 100 AT 690 V AC 5060 HZ CONFORMING TO IEC 60947-2 control type PUSHBUTTON [In] rated current 0.63...1 A thermal protection adjustment range 0.63...1 A magnetic tripping current 13 A [Ue] rated operational voltage 690 V AC 5060 HZ CONFORMING TO IEC 60947-2 [Ui] rated insulation voltage 690 V AC 5060 HZ CONFORMING TO IEC 60947-2 [Ith] conventional free air thermal current 1 A CONFORMING TO IEC 60947-4-1 [Uimp] rated impulse withstand voltage 6 KV CONFORMING TO IEC 60947-2 power dissipation per pole 2.5 W mechanical durability 100000 CYCLES electrical durability 100000 CYCLES FOR AC-3 AT 440 V operating rate 25 CYCH rated duty CONTINUOUS CONFORMING TO IEC 60947-4-1 direct connector WITHOUT connections - terminals SCREW CLAMP TERMINALS 2 CABLES 1...6 MM - CABLE STIFFNESS SOLID tightening torque 1.7 N.M - ON SCREW CLAMP TERMINALS suitability for isolation YES CONFORMING TO IEC 60947-1 phase failure sensitivity YES CONFORMING TO IEC 60947-4-1 height 89 MM width 44.5 MM depth 78.2 MM product weight 0.28 KG compatibility code GV2ME