MAIN CHARACTERISTICS range of product TESYS GV2 range TESYS product name TESYS GV2 device short name GV2LE product or component type CIRCUIT BREAKER device application MOTOR poles description 3P network type AC utilisation category CATEGORY A CONFORMING TO IEC 60947-2 network frequency 5060 HZ CONFORMING TO IEC 60947-2 breaking capacity 100 KA ICU AT 230240 V AC 5060 HZ CONFORMING TO IEC 60947-2 [Ics] rated service short-circuit breaking capacity 100 AT 690 V AC 5060 HZ CONFORMING TO IEC 60947-2 trip unit rating 1.6 A trip unit technology MAGNETIC magnetic tripping current 22.5 A COMPLEMETARY CHARACTERISTICS mounting mode BY CLIPS mounting support PLATE mounting position HORIZONTAL motor power kW 0.55 KW AT 400415 V AC 5060 HZ control type ROCKER LEVER [In] rated current 1.6 A [Ue] rated operational voltage 690 V AC 5060 HZ CONFORMING TO IEC 60947-2 [Ui] rated insulation voltage 690 V AC 5060 HZ CONFORMING TO IEC 60947-2 [Uimp] rated impulse withstand voltage 6 KV CONFORMING TO IEC 60947-2 power dissipation per pole 1.8 W mechanical durability 100000 CYCLES electrical durability 100000 CYCLES FOR AC-3 AT 415 V operating rate 40 CYCH rated duty CONTINUOUS CONFORMING TO IEC 60947-4-1 direct connector WITHOUT connections - terminals SCREW CLAMP TERMINALS 2 CABLES 1...6 MM - CABLE STIFFNESS SOLID tightening torque 1.7 N.M ON SCREW CLAMP TERMINALS mechanical robustness SHOCKS 30 GN CONFORMING TO IEC 60068-2-27 suitability for isolation YES CONFORMING TO IEC 60947-1 phase failure sensitivity YES height 89 MM width 45 MM depth 78.5 MM product weight 0.33 KG compatibility code GV2LE