MAIN CHARACTERISTICS range TESYS product name TESYS GB2 device short name GB2 product or component type CIRCUIT BREAKER device application CONTROL poles description 1P+N network type AC DC utilisation category CATEGORY A CONFORMING TO IEC 60947-2 network frequency 5060 HZ CONFORMING TO IEC 60947-2 breaking capacity ICU = 1 KA AT 48 V DC CONFORMING TO IEC 60947-2 [Ics] rated service short-circuit breaking capacity 75 AT 110 V AC 5060 HZ CONFORMING TO IEC 60947-2 trip unit technology THERMAL-MAGNETIC magnetic tripping current 108 A COMPLEMETARY CHARACTERISTICS mounting mode BY CLIPS mounting support PLATE mounting position HORIZONTAL control type TOGGLE [In] rated current 8 A [Ue] rated operational voltage 250 V AC 5060 HZ CONFORMING TO IEC 60947-2 [Uimp] rated impulse withstand voltage 4 KV CONFORMING TO IEC 60947-2 power dissipation per pole 2 W mechanical durability 8000 CYCLES electrical durability 8000 CYCLES connections - terminals CONNECTOR 1 CABLES 0.75...6 MM - CABLE STIFFNESS SOLID - WITHOUT CABLE END tightening torque 1.2 N.M - ON CONNECTOR mechanical robustness SHOCKS 22 GN FOR 20 MS CONFORMING TO IEC 60068-2-27 quantity per set SET OF 6 9 mm pitches 2 height 74 MM width 15 MM depth 67 MM product weight 0.07 KG compatibility code GB2