MAIN CHARACTERISTICS range of product MODICON X80 product or component type ANALOG INPUT MODULE electrical connection 2 CONNECTORS 40 WAYS Isolation between channels ISOLATED input level LOW LEVEL analogue input number 8 analogue input type VOLTAGE +- 1.28 V COMPLEMETARY CHARACTERISTICS analog/digital conversion SIGMA DELTA 16 BITS analogue input resolution 15 BITS + SIGN input impedance 10 MOHM permitted overload on inputs +- 7.5 V +- 1.28 V common mode rejection 120 DB 5060 HZ differential mode rejection 60 DB 5060 HZ cold junction compensation EXTERNAL BY PT100 PROBE type of filter FIRST ORDER DIGITAL FILTERING nominal read cycle time 200 MS WITH THERMOCOUPLE measurement error +- 0.7 DC NI 1000 25 DC temperature drift 25 PPMDC 400 OHM recalibration INTERNAL detection type OPEN CIRCUIT CU 10 maximum wiring resistance 20 OHM 2 WIRES CU 10 measurement resolution 0.1 DC CU 10 maximum conversion value +- 100 400 OHM status LED 1 LED GREEN RUN product weight 0.165 KG current consumption 150 MA AT 3.3 V DC