MAIN CHARACTERISTICS range of product IID range ACTI 9 product name ACTI 9 IID product or component type RESIDUAL CRRT CCT BRKER RCCB device short name IID poles description 4P neutral position LEFT [In] rated current 40 A network type AC earth-leakage sensitivity 500 MA earth-leakage protection time delay SELECTIVE earth-leakage protection class TYPE A SI COMPLEMETARY CHARACTERISTICS device location in system OUTGOER network frequency 50 60 HZ [Ue] rated operational voltage 380..415 V AC 5060 HZ residual current tripping technology VOLTAGE INDEPENDENT rated breaking and making capacity IDM 1500 A rated conditional short-circuit current 10 KA [Ui] rated insulation voltage 500 V AC 5060 HZ [Uimp] rated impulse withstand voltage 6 KV contact position indicator YES control type TOGGLE local signalling TRIP INDICATOR mounting mode CLIP-ON mounting support DIN RAIL comb busbar and distribution block compatibility TOOTH TOP OR BOTTOM connection pitch NO RENDITION 9 mm pitches 8 height 91 MM width 72 MM depth 73.5 MM product weight 0.37 KG colour WHITE mechanical durability 20000 CYCLES electrical durability 15000 CYCLES AC-1 locking options description PADLOCKING DEVICE connections - terminals SINGLE TERMINAL TOP OR BOTTOM RIGID WIRES 1...35 MM MAX wire stripping length 14 MM TOP OR BOTTOM tightening torque 3.5 N.M TOP OR BOTTOM compatibility code IID