MAIN CHARACTERISTICS range MASTERPACT range of product MASTERPACT NT product name MICROLOGIC product or component type CONTROL UNIT range compatibility MASTERPACT NT06...16 device application DISTRIBUTION poles description 3P network type AC network frequency 50 60 HZ trip unit name MICROLOGIC 6.0 A trip unit technology ELECTRONIC trip unit protection functions SELECTIVE E FAULT PROTECTION trip unit rating 630 A 50 DC protection type EARTH FAULT COMPLEMETARY CHARACTERISTICS mounting mode FIXED long time pick-up adjstment type Ir ADJUSTABLE long time pick-up adjustment range 0.4..1 IN long time delay adjustment type ADJUSTABLE 9 SETTING [tr] long-time delay adjustment range 0.7..16.6 S 7.2 X IR thermal memory 20 MN short-time pick-up adjustment type Isd ADJUSTABLE 9 SETTING [Isd] short-time pick-up adjustment range 1.5..10 X IR short-time delay adjustment type ADJUSTABLE 5 SETTING [tsd] short-time delay adjustment range 0.02...0.5 S instantaneous pick-up adjustment type Ii ADJUSTABLE instantaneous pick-up adjustment range 2..15 X IN ground-fault time delay adjustment type -tg ADJUSTABLE 5 SETTINGS ground-fault pick-up adjustment type ADJUSTABLE 9 SETTINGS [tg] ground-fault time delay adjustment range 0...0.4 S [Ig] ground-fault pick-up adjustment range 0.2...1 X IN 400 A < IN < 1250 A zone selective interlocking ZSI WITH display type DIGITAL DISPLAY type of measurement AMMETER