MAIN CHARACTERISTICS range MASTERPACT range of product MASTERPACT NT product name MASTERPACT NT product or component type BASIC FRAME device short name MASTERPACT NT06 circuit breaker name MASTERPACT NT06L1 poles description 4P neutral position LEFT network type AC breaking capacity code L1 suitability for isolation YES CONFORMING TO IEC 60947-2 utilisation category A COMPLEMETARY CHARACTERISTICS network frequency 50 60 HZ control type PUSHBUTTON mounting mode FIXED [In] rated current 630 A 40 DC [Ui] rated insulation voltage 1000 V AC 5060 HZ CONFORMING TO IEC 60947-2 [Uimp] rated impulse withstand voltage 12 KV CONFORMING TO IEC 60947-2 [Icm] rated short-circuit making capacity 220 KA 525 V AC 5060 HZ [Ue] rated operational voltage 690 V AC 5060 HZ CONFORMING TO IEC 60947-2 circuit breaker CT rating 630 A breaking capacity 100 KA ICU AT 525 V AC 5060 HZ CONFORMING TO IEC 60947-2 [Ics] rated service breaking capacity ICS 100 KA 525 V AC 5060 HZ CONFORMING TO IEC 60947-2 protection type WITHOUT PROTECTION mechanical durability 12500 CYCLES WITHOUT MAINTENANCE CONFORMING TO IEC 60947-2 electrical durability AC-23A : 3000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 connection pitch 70 MM [Icw] rated short-time withstand current 10 KA 0.5 S CONFORMING TO IEC 60947-2 integral instant protection 5.67...6.93 KA maximum breaking time 9 MS closing response time < 50 MS height 301 MM width 346 MM depth 196 MM compatibility code NT06