MAIN CHARACTERISTICS range of product RED range of product ACTI 9 product or component type RESIDUAL CRRT CCT BRKER RCCB device short name REDS protection type RECLOSER poles description 2P neutral position LEFT signal contacts composition 1NO OR 1NC OR INTERMITTENT 1HZ [In] rated current 63 A earthing system TN-S network type AC earth-leakage sensitivity 30 MA COMPLEMETARY CHARACTERISTICS device location in system OUTGOER network frequency 50 HZ [Ue] rated operational voltage 230 V AC 50 HZ PHASE TO NEUTRAL reset FAULT RESET EARTH LEAKAGE test function MANUAL AT 100 V earth-leakage protection time delay INSTANTANEOUS earth-leakage protection class TYPE A leakage resistance 10 KOHM [Im] rated making and breaking capacity IDM 630 A 230 V rated conditional short-circuit current gL63 : Inc 6 kA 63 A gL [Ui] rated insulation voltage 500 V [Uimp] rated impulse withstand voltage 4 KV control type TOGGLE local signalling 2 LEDS type of setting INSUL FLT PRESENCE MONITORING signalling circuit voltage AC 5...230 V mounting mode FIXED mounting support 35 MM SYMMETRICAL DIN RAIL 9 mm pitches 8 height 115 MM width 71 MM depth 79.5 MM product weight 0.36 KG mechanical durability 1000 CYCLES OPEN-CLOSE connections - terminals GUARD TUNNEL TERMINAL 35 MM RIGID auxiliary connection terminal TUNNEL TYPE TERMINAL FLEXIBLE 2.5 MM wire stripping length 12 MM tightening torque power circuit : 2 N.m compatibility code REDS