Product Name: NG5001 Nominal voltage: 8.2 DC, (1kΩ) V Electrical design: Connection to certified intrinsically safe circuits with the max. values U = 15 V / I = 50 mA / P = 120 mW Switching frequency: 720 Hz Sensing range: 5 mm Length: 33 mm Ambient temperature: -20...80 °C Shortcode: IG-2005-N/1D/1G SKU JWYFPGIPFJPLD2 Output function: Normally closed Housing materials: PBT Current rating: < 30, when used outside the hazardous area mA Marking of the unit: ExII 1G Ex ia IIB T6 Ga ExII 2G Ex ia IIC T6 Gb ExII 1D Ex ia IIIC T 90°C Da Protection: IP 67 Connection: PVC cable / 2 m, 2 x 0.5 mm² Mounting: flush mountable